MTP/MPO Harness Assemblies

Ascent’s single-mode and multi-mode MPO/MTP® products are multi fiber connectors used in high-density backplane and Printed Circuit Board (PCB) applications in data and telecommunications system.

    24-core MPO - 12xLC duplex multiple fiber assembly

    Single-mode & multi-mode available

    New miniature Breakout Module - saving space within patching management area the same time providing robust and safe transition between cable and tails

    Female MTP/MPO connectors for direct connection into QSFP + transceiver

    LSZH, OFNP, OFNR cable jacket types selection

    Rapid deployment Factory terminated modular system saves installation and reconfiguration time during moves, ads and changes

    Reliability 100 % tested - combination of high-quality components and manufacturing quality control guarantees product to the highest standards

    The fiber types are SM (G657A1), MM (OM3/OM4)


Fiber Transmission Performance


Multi‑mode

Single‑mode

Fiber Type

62.5/125μm

(850/1300nm)

50/125μm

(850/1300nm)

50/125μm

(850/1300nm)

50/125μm

(850/1300nm)

Single‑mode

(1310/1383/1550nm)

ISO/IEC name

OM1

OM2

OM3

OM4

OS2

Maximum Attenuation (dB/km)

3.4/1.0

3.0/1.0

3.0/1.0

3.0/1.0

0.4/0.4/0.3*

Maximum Attenuation (dB/km)

3.4/1.0

3.0/1.0

3.0/1.0

3.0/1.0

0.65/0.65/0.5**

Minimum Over Filled Launch (OFL) Bandwidth (MHx•km)

200/500

700/500

1500/500

1500/500

/

Minimum Effective Modal

Bandwidth (MHx•km)

220 / ‑

950 / ‑

2000 / ‑

5350 / ‑

/

Characteristics


Multi‑mode (at 850/1300nm)

Single‑mode (at 1310/1550nm)

MTP®/MPO Connector Insertion Loss

Typical 0.50 dB

Maximum 0.75 dB

Typical 0.45 dB

Maximum 0.55 dB

MTP®/MPO Connector Reflectance

<25 dB

<35dB (8o angled polish)

Durability

500 rematings: < 0.50dB change

500 rematings: < 0.45 dB change

Operating Temperature1

Outdoor cable: ‑40 °C to +70 °C

Indoor cable: 0 °C to +70 °C

 

Length

Length as defined in P/N, XX meters.

Tolerance: < 5.0 meters +5/‑0 cm; ≥ 5.0 meters +20/‑0 cm

Loose tube cables include a transition at one or both ends that is included in overall length.







Note 1: Contact customer service representative to discuss exceptional environmental conditions


448-2.jpeg