Ascent’s ALA series Lead Acid 12V 150Ah VRLA UPS batteries are widely used in standby power applications for telecommunications, UPS, military, broadcast, and television system purposes.
• AGM VRLA sealing technology
• High discharge performance
• High gas recombination efficiency
• Maximum charge efficiency
• Low self-discharge rate
• Easy installation and handling
ALA‑MT‑150‑12
Item | Description |
Nominal Voltage | 12 V |
Nominal Capacity (10 h) | 150.0 Ah |
Rated Capacity (+25 °C) | 20 h rate (7.94 A, 1.80 V): 159.0 Ah 10 h rate (15.0 A, 1.80 V): 150.0 Ah 8 h rate (18.1 A, 1.80 V): 144.8 Ah 5 h rate (27.3 A, 1.75 V): 136.5 Ah 1 h rate (101.0 A, 1.67 V): 101.0 Ah |
Internal Resistance | Approx. 3.7 mΩ |
Maximum Discharge Current | 1200 A/5s |
Cycle Use (+25 °C) | Initial Charging Current: ≤45.0 A Voltage: 14.4 V to 15.0 V Temp. coefficient: ‑30 mV/°C |
Standby Use (+25 °C) | No limit on Initial Charging Current Voltage: 13.5 V to 13.8V Temp. coefficient: ‑18 mV/°C |
Capacity Affected by Temperature | +40 °C: 103% +25 °C: 100% 0 °C: 86% |
Self‑Discharge | MT series batteries may be stored for up to 6 months at +25 °C before a freshening charge is required. For higher temperatures the time interval will be shorter. |
Terminal | T8 |
Container Material | ABS |
Operating Temperature | Discharge: ‑15 °C to +50 °C Charge: 0 °C to +40 °C Storage: ‑15 °C to +40 °C |
Nominal Operating Temperature | 25 °C ± 3 °C |
Dimensions (L × W × H) | 550 mm × 125 mm × 280 mm (280 mm total height) |
Approx. Weight | 50.6 kg |
Get in touch with our experts